- Overview
- Product Description
- Product Parameters
- Certifications
- Packaging & Shipping
- Installation Instructions
- Company Profile
- FAQ
Basic Info.
Model NO.
EPJS Series
Display
LCD
Control
Computer Control
Weight
22kg
Power Source
AC220V
Printer
Build-in Thermal Printer
Anti-Interference Principle
Frequency Conversion
High Voltage Output
0.5kv~12kv
Precision
0.1
Maximum Current
200mA
Capacity
2000va
Self-Excitation Power
AC 0V~50V/15A
Automatic Double Frequency
45Hz/55Hz 47.5Hz/52.5Hz 55Hz/65Hz 57.5Hz/62.5Hz
Tg Resolution
0.001%
Cx Resolution
0.001PF
Tg Accuracy
+-(Reading*1.0%+0.040%)
Cx Accuracy
+-(Reading*1.0%+1.00PF)
Tg Measurement Range
Without Limit
Cx Measurement Range
15PF Less Cx Less 300NF
12kv Measurement Range
Cx Less 30 NF
Transport Package
Plywood Case with Foam and Waterproof Plastics
Specification
460*360*350mm
Trademark
EP Hipot Electric
Origin
Wuhan, China
HS Code
9031809090
Production Capacity
500/Year
Product Description
Transformers High-voltage (HV) cables switchgear (GIS) systems Tan Delta Test Kit CP TD output voltages up to 12 kV
More details on 12kV C&DF Tester please contact EPHipot Electric, we have professional tech team to design correctly designed products and systems.
General Information:
EPJS-6000 is a new generation, fully automatic on-site measure dielectric loss(tgδ)and the capacitance (Cx) of electric equipment. It's suitable for testing on transformer, insulating bush, capacitor, CT/PT, MOA etc.
Features:
- Build-in dielectric loss bridge, frequency conversion power supply, testing transformer, SF6 high stability standard capacitor.
- The test high-voltage source is generated by the inverter inside the instrument and is used for the test object after boosting the voltage from the transformer.
- Frequency can be changed into 50Hz, 47.5Hz/52.5Hz, 45Hz/55Hz, 60Hz, 57.5Hz/62.5Hz, 55Hz/65Hz. Digital notch technology is adopted to avoid the interference of power frequency electric field to the test.
- Multiple protection of input voltage fluctuation, output short circuit, over-voltage, over-current, temperature, secure and reliable. Meanwhile, it has the function of grounding testing, that voltage boost is not permitted for non-grounding equipment.
- LCD touch screen display. English menu easy to operate.
- 200 groups' data storage. Save testing result according to time order, check history record and print the result.
- Multiple testing mode, with modes of inside high voltage, outside high voltage, inner standard, external standard, GST/UST, self-excitation. High voltage (more than 12kV) dielectric loss test can be made in the situation of external standard outside high voltage.
- Test full sealed CVT (Capacitive Voltage Transformer) C1 and C2 dielectric loss and capacitance at the same time. Also test CVT transformation ratio and voltage angle difference.
- The instrument can accurately measure the CVT dielectric loss value and capacitance value without removing the CVT high voltage lead.
- The dielectric loss and capacitance value of C0 in the upper end of CVT can be measured by using the reverse shielding method.
- High speed sampling signal. Inverter and sampling circuit inside are digitized controlled. Output voltage is adjusted continuously.
Working condition | -15ºC~40ºC | RH<80% | |
Anti-interference principle | Frequency conversion | ||
Power supply | AC 85V~160V | Generator can be used | |
High voltage output | 0.5kV~12kV | Every 0.1kV | |
Precision | 2% | ||
Maximum current | 200mA | ||
Capacity | 2000VA | ||
Self-excitation power | AC 0V~50V/15A | 45HZ/55HZ 47.5HZ/52.5HZ 55HZ/65HZ 57.5HZ/62.5HZ Automatic double frequency | |
Resolution | tgδ: 0.001% | Cx: 0.001pF | |
Accuracy | △tgδ:±(Reading*1.0%+0.040%) | ||
△Cx :±(Reading*1.0%+1.00PF) | |||
Measurement range | tgδ | Without limit | |
Cx | 15pF < Cx < 300nF | ||
12kV | Cx < 30 nF | ||
5kV | Cx < 150 nF | ||
1kV | Cx <300 nF | ||
CVT test | Cx < 300 nF | ||
CVT ratio range | 10~10000 | ||
CVT ratio accuracy | 0.1% | ||
CVT ratio resolution | 0.01 | ||
Storage | 200 group supports U disk data storage | ||
Dimension | Main unit: 350(L)×270(W)×270(H) | ||
Accessory box: 350(L)×270(W)×160(H) | |||
Weight | Main unit: 22.75kg | ||
Accessory box: 5.25kg |
More details on 12kV C&DF Tester please contact EPHipot Electric, we have professional tech team to design correctly designed products and systems.